Ultrabook, Celeron, Celeron Inside, Core Inside, Intel, Intel Logo, Intel Atom, Intel Atom Inside, Intel Core, Intel Inside, Intel Inside Logo, Intel vPro, Itanium, Itanium Inside, Pentium, Pentium Inside, vPro Inside, Xeon, Xeon Phi, Xeon Inside, and Intel Optane are trademarks of Intel Corporation or its subsidiaries in the U.S. and/or other countries.
Overview
Serviceability
-
User-replaceable batteries
Increases availability by allowing a trained user to perform upgrades and replacements of the batteries reducing Mean Time to Repair (MTTR)
-
User-replaceable power modules
Enables simple upgrades and replacements of the Power Modules.
-
Disconnected battery notification
Warns when a battery is not available to provide backup power.
-
Automatic self-test
Periodic battery self-test ensures early detection of a battery that needs to be replaced.
-
Predictive failure notification
Provides early-warning fault analysis ensuring proactive component replacement.
-
User-replaceable intelligence modules
Enables simple upgrades and replacements of the Intelligence Modules.
-
Audible alarms
Actively let you know if the unit is on battery, if the battery is low or if there is an overload condition.
Scalability
-
Programmable frequency
Ensures compatibility with different input frequencies.
-
Field-replaceable power distribution panel
Ensures compatibility with equipment that has different plug types.
-
Plug-and-Play external batteries
Ensures clean, uninterrupted power to the loads when adding extra runtime to the UPS.
-
Scalable runtime
Allows additional run time to be quickly added as needed.
-
Scalable power capacity
Reduces UPS over-sizing costs today by allowing quick power upgrades, within the same footprint, later.
Spesifikasi
Output
-
Output power capacity
2.8 KWatts / 4.0 kVA
-
Max Configurable Power (Watts)
5.6 KWatts / 8.0 kVA
-
Nominal Output Voltage
230V
-
Output Voltage Note
Configurable for 220 : 230 or 240 nominal output voltage
-
Output Voltage Distortion
Less than 5% at full load
-
Output Frequency (sync to mains)
47 - 63 Hz
-
Output Frequency (not synced)
60Hz +/- 0.1% for 60Hz nominal, 50Hz +/- 0.1% for 50Hz nominal
-
Other Output Voltages
220, 240
-
Load Crest Factor
up to 5 : 1
-
Topology
Double Conversion Online
-
Waveform type
Sine wave
-
Maximum Output Current
18
-
Output Connections
(1) Hard Wire 3-wire (H N + G) (Battery Backup)
-
Bypass
Internal Bypass (Automatic and Manual)
Input
-
Nominal Input Voltage
230V , 400V 3PH
-
Input frequency
45 - 65 Hz (auto sensing)
-
Input Connections
Hard Wire 3 wire (1PH+N+G), Hard Wire 5-wire (3PH + N + G)
-
Input voltage range for main operations
155 - 276 (1:1), 290 - 480 (3:1)V
-
Input Total Harmonic Distortion
Less than 7% for full load
-
Other Input Voltages
220V, 240V, 380V, 415V
-
Input Power Factor at Full Load
0.98